Danfoss AK-SM800A: six unpatched flaws give unauthenticated remote root takeover (no CVE)
Severity: critical · Patch status: unpatched · Since 2026-11-16
Midnight Blue researcher Carlo Meijer found six pre-authentication flaws in the Danfoss AK-SM800A supervisory controller in under an hour of manual review of firmware the vendor publishes, and says every version up to and including 5.3.2 is affected. All six are stack-based buffer overflows. Five sit in web request handlers that need no login, inside a process that runs as root; on firmware 3.3.0 one of them was turned into code execution as root, and the same bugs are present in 5.3.2. The sixth is in the gateway that enforces Strict mode; under emulation with Strict mode on it crashed, which the researchers say could be turned into code execution, and the gateway has no stack canaries. Root access would let an attacker change settings, start defrost cycles, hide activity from logs and plant code that survives a factory reset, since the controller has no secure boot. No CVE IDs have been assigned. The vendor's advisory page listed nothing for these flaws as of 2026-11-16, and the researchers say firmware 5.4.0 does not fix them. The researchers are withholding technical details during coordinated disclosure with Danfoss. Belgian, Irish and German authorities tell operators to remove internet exposure of the management interface, including via 4G/5G modems, and not to rely on firmware updates or Strict mode. BSI says it has no information on exploitation of these six flaws, and neither other agencies nor the researchers link them to the attack waves on Danfoss and Copeland/Dixell controllers that began in France on 11 October.
What to do
- Immediately remove all internet exposure of AK-SM800A management interfaces, including via 4G/5G modems, regardless of firmware version or Strict mode
- Restrict remote access to a secure VPN or protected internal network; firewall allowlisting of service-company IPs only as a short-term measure
- Check temperature setpoints, defrost schedules, alarm settings, user accounts and remote-access settings for unauthorized changes
- If compromise is suspected, change all credentials and verify connected equipment works properly
- Run latest supported firmware, change default passwords and enable Strict mode, but do not rely on these alone
- Before cutting data feeds to the refrigeration service company, check contract and insurance terms and set up protected remote access so monitoring continues